ELSR-N
Self-regulating heating cable
Usage
- Frost protection and heating products
- Power range 10-40 W/m
- Available in different designs for many uses
-
65 °C
-
80 °C
-
EX
-
Can be cut and crossed for perfect adaptation
-
UV-resistant
Self-regulating heating cable ELSR-N is suitable for frost protection and temperature maintenance for industrial use in the low temperature range. It is also approved for use in hazardous areas, EX areas. The BOT version of this heating cable is also resistant to reactive chemicals, oil and fuel. Thanks to the high chemical resistance, the cable also has a long service life.
ELSR-N
Specifications
Specification | Data |
---|---|
Connection voltage | 230 V |
Number of conductors | 2 pcs |
Bending radius, min. | 25 mm |
Exposure temperature (power off), max. | 80 ºC |
Exposure temperature (power on), max. | Up to 65 ºC |
-AO | Protective conductor: Aluminium foil, Outer casing: TPE |
-BO | Protective conductor: Braided, Outer casing: TPE |
-BOT | Protective conductor: Braided, Outer casing: Fluoropolymer |
Installation temperature, min. | -60 ºC |
Insulation material outer | TPE-O |
Cable type | Self-regulating 2-conductor with screen |
Classification (Ex) | II 2G Ex 60079-30-1 IIC GbII 2D Ex 60079-30-1 IIIC Db |
Conductor area | 1,23 mm² |
Installation
*¹ Heating circuit lengths on the following conditions
- 230 V nominal voltage
- Delayed action circuit breakers (C-characteristic) with 80 % max. load
- Maximum 10 % line voltage drop on heating cable bus wire
- Power connection to one heater end
- In certain installation situations, the heating circuit length may vary. Please contact our engineers.