ELSR-H

ELSR-H

Self-regulating heating cable

Usage

  • Frost protection and heating products
  • Power range 10-75 W/m
  • Wide range of uses
  • Power on: 120 °C
    120 °C
  • 210 °C
    210 °C
  • EX
    EX
  • Can be cut and crossed for perfect adaptation
  • High chemical resistance
  • High temperature resistance
The self-regulating heating cable ELSR-H for high temperatures (up to 210°C ) has a large number of industrial applications. In addition to high temperatures, the cable is also suitable and approved for use in hazardous areas. The BOT version of this heating cable is also resistant to reactive chemicals, oil and fuel. Thanks to the high chemical resistance, the cable also has a long service life.

ELSR-H

Specifications

Specification Data
Connection voltage 230 V
Number of conductors 2 pcs
Bending radius, min. 25 mm
Exposure temperature (power off), max. 210 ºC
Exposure temperature (power on), max. Up to 120 ºC
-BOT Protective conductor: Braided, Outer casing: Fluoropolymer
Installation temperature, min. -60 ºC
Insulation material outer PFA
Cable type Self-regulating 2-conductor with screen
Classification (Ex) II 2G Ex 60079-30-1 IIC GbII 2D Ex 60079-30-1 IIIC Db
Conductor area 1,23 mm²

Warranty

The general terms of delivery are listed below.

Our warranty terms

Installation

ELSR-H graf

 *¹ Heating circuit lengths on the following conditions

  • 230 V nominal voltage
  • Delayed action circuit breakers (C-characteristic) with 80 % max. load
  • Maximum 10 % line voltage drop on heating cable bus wire
  • Power connection to one heater end
ELSR-H graf

 

Supplementary products