ELP/PFA

Parallel-resistive 2-conductor with screen

Usage

  • Power range 15-60 W/m
  • Frost protection and heating products
  • Constant effect
  • Power on: 160-205 °C
    160-205 °C
  • Power off: 260 °C
    260 °C
  • EX
    EX
  • Can be cut during installation for good fit
  • UV-resistant
This parallel-resistive heating cable is flexible to use as it can easily be cut to the desired length from the reel and thus ensure a constant output power. No connection cable is required and the input can be made from one end. Assembly is quick and easy, which significantly reduces costs. The output can be up to 60 W/m as these ELP parallel heating cables are routed along pipes, they are particularly suitable for pipelines with high output requirements, e.g. in industrial process technology. The particularly temperature-resistant outer jacket made of PFA and the high chemical resistance of PFA ensure a long service life.

ELP/PFA

Article list

Article number Description Dimensions W x H (mm) Exposure temperature (power on), max. (ºC) Output (W/m)
8935251 ELP/PFA 15 BOT 8 x 5,5 205 15
8935252 ELP/PFA 30 BOT 8 x 5,5 190 30
8935253 ELP/PFA 45 BOT 8 x 5,5 175 45
8935254 ELP/PFA 60 BOT 8 x 5,5 160 60

Specifications

Specification Data
Connection voltage 230 V
Number of conductors 2 pcs
Bending radius, min. 25 mm
Exposure temperature (power off), max. 260 ºC
Exposure temperature (power on), max. Up to 205 ºC
-BOT Protective conductor: Braided, Outer casing: Fluoropolymer
Contains SVHC substances according to REACH No
Installation temperature, min. -45 ºC
Insulation material intermediate Fluoropolymer
Insulation material inner Fluoropolymer
Insulation material outer PFA
Cable type Parallel-resistive 2-conductor with screen
Contact distance 1 m
Conductor area 1,50 mm²

Warranty

The general terms of delivery are listed below.

Our warranty terms