ELSR-Ramp
Self-regulating heating cable
Usage
- For snow melting, ground
- Laid in a sand bed or embedded in concrete
-
Cable
-
80 °C
-
100 ºC
-
High power per meter
-
Can be cut during installation for good fit
-
Can be crossed during installation
The self-regulating heating cable ELSR-Ramp is intended for embedding in concrete for outdoor snow melting, such as in parking garages, ramps, and stairs.
ELSR-Ramp
Specifications
Specification | Data |
---|---|
Connection voltage | 230 V |
Number of conductors | 2 pcs |
Bending radius, min. | 50 mm |
Output | 50 W/m at 10 ºC, 110 W/m at 5 ºC (embedded in concrete) |
Exposure temperature (power off), max. | 100 ºC |
Exposure temperature (power on), max. | Up to 80 ºC |
-BO | Protective conductor: Braided, Outer casing: TPE |
Installation temperature, min. | -20 ºC |
Insulation material outer | TPE |
Cable type | Self-regulating 2-conductor with screen |
Conductor area | 2,77 mm² |
Installation

*¹ Heating circuit lengths on the following conditions
- 230 V nominal voltage
- Delayed action circuit breakers (C-characteristic) with 80 % max. load
- Maximum 10 % line voltage drop on heating cable bus wire
- Power connection to one heater end
- In certain installation situations, the heating circuit length may vary. Please contact our engineers.